Indoor unit installationAttentionFixing the Installation PlateDrilling the Hole1. Install the installation plate horizontally over the structural par
Connective pipe and drainage installationDrainage1. Run the drain hose sloping downward. Do not install the drain 2. When connecting extension drain
AttentionPiping and wrapping1. Bundle the tubing, connecting cable, and drain hose with tape 2. Because the condensed water from rear of the indoor
1. Install the outdoor part of the unit on a rigid surface to avoid excess noise and vibration.2. Direct the air vent toward an area without obstacl
Settlement of outdoor unitAnchor the outdoor unit tightly and horizontally on a concrete or rigid Air inletAirinletAir outlet$%mount with a bolt and n
Flaring workMain cause for refrigerant leakage is due to defect in the flaring work.Carry out correct flaring work using the following procedure:1. C
4. Flaring work.die in the dimension shown in the table below.OUTERConnection Adjustment1. Align the pipes to be connected.OUTER TIGHTENINGCaution:
OperatingVoltage(Min/Max)RLA LRA FLA HPOutputWattsVolts FLA HPOutputWatts9K 115-1-60ǂ103/127 16.03 26 0.17 0.04 30 115V-AC 0.38 0.03 20 2212K 115-1-60
1. The inside and outside connecting cable can be connected without removing the front grille.2. Connecting cable between indoor unit and outdoor un
1.
Safety precautions04Safety precautionsDANGER! Avoid Serious InjuryThis appliance must be installed by a qualified licensed HVAC technician in accordan
1. Never fail to have an individual power circuit specifically for the air conditioner. As for the method of wiring, be guided by the circuit diagram
Air purging with vacuum pump1. Check that each tube(both liquid and gas side tubes) between the indoor and outdoor units have been properly connected
Air purging24Vacuum pumpCharge hoseManifold valve-76cm/HgChargehoseHandle LoHandle HiOutdoor unitIndoor unitWhen using the vacuum pumpFor method of us
Electrical safetyPerform the electric safety check after completing installation:Gas leak checkSoap water methodApply a soap water or a liquid neutral
Test runningPerform test operation after completing gas leak check at the flare nutconnections and electrical safety check.1. Connect the power, pres
1. Contact a specialist to install the device.2. Guarantee that the unit is appropriately fastened and complies with all of the aforementioned safet
To prevent injury to the user or other people and property damage, the following instructions must be followed.Incorrect operation due to ignoring of
operation. It may cause electric removed, do not touch the metal parts of the unit. It may cause an injury.shock or injury.and electric shock.It may c
Precautions for InstallationInstallation at the following sites may cause problems. If you must inevitably install 2. Sites with a high concentratio
Outdoor Unit1. The outdoor unit must be installed at a convenient site that is not exposed to strong winds. The site should be dry and well ventilate
Attention1. This illustration is for explanation purposes only.431Indoor unitOutdoorunit56Air filterMoreABC2. Copper tubes must be insulated indepen
1.58''7.91''5.31''1.58''AB (A:33.31" B:10.83")=18000 Btu's (A:36.97" B:11.73")Ind